| Model Number | Voltage | Surge Capacity | Protection Modes | Clamping Voltage |
| PSA/120Y | 120/208, 3-phase, Wye | 160,000 Amps/phase | L-N, L-G, N-G | L-N
= 330V L-G = 330V N-G = 330V |
| PSA/277Y | 277/480, 3-phase, Wye | 160,000 Amps/phase | L-N, L-G, N-G | L-N
= 600V L-G = 600V N-G = 600V |
| PSA/480D | 480, 3-phase, Delta | 160,000 Amps/phase | L-G, L-L | L-G
= 1500V L-L = 1500V |
| PSB/120Y | 120/208, 3-phase, Wye | 240,000 Amps/phase | L-N, L-G, N-G | L-N
= 330V L-G = 330V N-G = 330V |
| PSB/277Y | 277/480, 3-phase, Wye | 240,000 Amps/phase | L-N, L-G, N-G | L-N
= 600V L-G = 600V N-G = 600V |
| PSB/480D | 480, 3-phase, Delta | 240,000 Amps/phase | L-G, L-L | L-G
= 1500V L-L = 1500V |
| PSC/120Y | 120/208, 3-phase, Wye | 320,000 Amps/phase | L-N, L-G, N-G | L-N
= 330V L-G = 330V N-G = 330V |
| PSC/277Y | 277/480, 3-phase, Wye | 320,000 Amps/phase | L-N, L-G, N-G | L-N
= 600V L-G = 600V N-G = 600V |
| PSC/480D | 480, 3-phase, Delta | 320,000 Amps/phase | L-G, L-L | L-G
= 1500V L-L = 1500V |
Secondary Distribution/At the Load Systems Single Unit Systems
| Model Number | Voltage | Surge Capacity | Protection Modes | Clamping Voltage |
| PSD/120Y | 120/208, 3-phase, Wye | 80,000 Amps/phase | L-N, L-G, N-G | L-N
= 330V L-G = 330V N-G = 330V |
| PSD/277Y | 277/480, 3-phase, Wye | 80,000 Amps/phase | L-N, L-G, N-G | L-N
= 600V L-G = 600V N-G = 600V |
| PSD/480D | 480, 3-phase, Delta | 80,000 Amps/phase | L-G, L-L | L-G
= 1500V L-L = 1500V |
| PSD/240D | 240, 3-phase, Delta | 80,000 Amps/phase | L-G, L-L | L-G
= 700V L-L = 700V |
| PSD/120/240S | 120/240 split phase | 80,000 Amps/phase | L-N, L-G, N-G | L-N
= 330V L-G = 330V N-G = 330V |
| PSE/120Y | 120/208, 3-phase, Wye | 50,000 Amps/phase | L-N, L-G, N-G | L-N
= 330V L-G = 330V N-G = 330V |
| PSE/277Y | 277/480, 3-phase, Wye | 50,000 Amps/phase | L-N, L-G, N-G | L-N
= 600V L-G = 600V N-G = 600V |
| PSE/120/240S | 120/240, split phase | 50,000 Amps/phase | L-N, L-G, N-G | L-N
= 330V L-G = 330V N-G = 330V |

.gif)