TRANSIENT VOLTAGE SURGE SUPPRESSION
Guideform Specification
PSA TVSS Cut Sheet / PSB TVSS Cut Sheet / PSC TVSS Cut Sheet
PSD TVSS Cut Sheet / PSE TVSS Cut Sheet
System Description
The Series TVSS has been designed to respond to the many applications where the cause or threat can be attributed to a specific source or piece of equipment. When that occurs and the cause is surge, then a surge suppression device (TVSS) may be all that you need. It is very cost effective and can be installed to protect a specific load or one specific piece of equipment. PS&C offers a UL 1449 Second Edition listed TVSS product line. The range of this line starts at the Service Entrance/Main Distribution panel up to 320kA per phase and goes down to the Secondary Distribution/At the Load up to 80kA per phase. With MOV-based technology, these systems provide many options to get maximum value for you power protection investment. PS&C surge suppression products can be selected to build a layered protection scheme for all critical points within the facility. All PS&C surge suppression systems include:Design Features
- UL 1449 Second Edition Listed
- EMI/RFI filtering
- Protection in all modes
- On-line monitoring
- Superior clamping voltages
- Dry contacts for remote monitoring
- Tested to exceed industry standards for longevity
- Thermal cutout for over voltage and high fault current protection
- Fusing in each suppression mode
- 5-year unlimited replacement warranty
PSA, PSB, & PSC: Service Entrance/Main Distribution
Modules PSA, PSB and PSC offer redundant replaceable modules in each phase, guaranteeing continuous service of the unit. Protection is provided in all modes
- 160kA to 320kA per phase
- Category C3 tested (5,000 impulses)
- Individually fused modules
- Replaceable fusing
- Copper bus bar connections
- Surge counter, LED indicators
- Audible alarm, with test and reset switch
- Dry contacts with summary alarm
- Thermal cut-out for over voltage and high fault current protection
- EMI/RFI filtering
- NEMA12 enclosure: 16x14x6 inches (40.6x35.6x15.2 cm),15 48 lbs (21.8 kg)
PSD & PSE: Secondary Distribution/At the Load
Models PSD and PSE offer a second or third line of defense to service entrance and main distribution systems. With a lower cost of investment, these TVSS units are perfect for lighting panels or for placement on individual loads.